Fan Classification - AMCA

Fan Classification - AMCA


Fan classification established by AMCA

AMCA - Air Movement and Control Association International fan-class standards are established to simplify the specification of fans. AMCA fan-class standards are based on fan horsepower required per square foot of outlet area representing the structural requirements imposed on a fan for a given set of operating conditions.
AMCA class limits for a double-width airfoil centrifugal fan:
AMCA
Fan Class
Lower RangeUpper Range
Static Pressure
(in W.G.)
Outlet Velocity
(ft/min)
Static Pressure
(in W.G.)
Outlet Velocity
(ft/min)
I2.532005.02300
II4.2541758.53000
III6.75525613.53780

AMCA Fan Classes I II III - Static Pressure vs. Outlet Vleocity

Example - Classification of Fan

AMCA Fan Classes I II III - Static Pressure vs. Outlet Vleocity - Example

A fan working with static pressure 4.5 in W.G. and outlet velocity 3500 ft/min is within AMCA Fan Class II.  